BCI Lift Station Pro

The BCI LSPro system is complete duplex/triplex lift station controller with support for multiple station configurations and options. At the heart of this system is the Schneider Electric SCADAPack 334 E Series RTU. Combined with the Schneider Electric TeSys-T Motor Management system, the LSPro system can provide power data.

  • Duplex/Triplex Pump Controller
  • Float or Level Transducer (4-20ma) Control
  • Pump Alternation
  • Pump Power Data (KWH, Amps, Voltage) with optional TeSys T
  • Optional Local HMI and Configuration

LSPro Standard Features
  • DNP3 and Modbus Communication
  • RTU Event Logging (20000 events when utilizing DNP3 Protocol)
  • Serial and Ethernet Connectivity
  • USB Configuration
  • 16 Digital Inputs
  • 10 Dry Contact Relay outputs
  • 8 Analog Inputs (4-20ma)
  • Multiple communication options (Conventional Radio, Spread Spectrum, Ethernet, Cellular)

LSPro I/O
  • Pump Run and Fail inputs
  • Pump Start/Stop
  • Pump HOA Switch status
  • Float Status
  • Generator Run/Fail inputs
  • Generator Start/Stop
  • Generator Fuel Level (4-20 input, signal supplied by customer)
  • Phase Monitor / Utility Power
  • Local Horn/Light control
  • Level Transducer

LSPro Telemetry Panels

Standard LSPro Telemetry Panel


Expanded LSPro Telemetry Panel includes two TeSys-T Modules


LSPro Specifications (SCADAPack RTU)
  • Input Power: 11 - 30VDC, 3.5W typical
  • Environment : –40°C (–40°F) to 70°C (158°F)
  • Packaging: Corrosion resistant zinc-plated steel with black enamel paint
  • Analog Inputs: 8, 0-20/4-20mA / 0-5/0-10V
  • Analog Inputs: 8, 0-20/4-20mA / 0-5/0-10V
  • Digital I/O :
    • 16 inputs: 12/24V,48V, 115/125V, 240V digital inputs
    • 10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC
  • I/O Terminations: 5, 6 and 9-pole removable terminal blocks, 12 to 22AWG, 15a contacts
  • Dimensions: 5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep
(Specifications for other components available by request)